Dealing with short circuits in the footwell module, FRM, 2nd generation
Note:
Dealing with short circuits in the footwell module depends on the date of manufacture of the footwell module. Differences result for the date of manufacture 09/2007.
Description of dealing with short circuits up to 09/2007:
If a short circuit is detected in a power circuit, this power circuit is switched off after one minute. This power circuit remains switched off until there has been a terminal change (terminal 15 > terminal 30 -> terminal 15).
A renewed attempt to switch on is only made after a terminal change.
The footwell module permanently switches off the corresponding output if a total of 50 terminal changes have taken place while there is a short circuit in a power circuit. This is the case if the fault memory entry can no longer be deleted even though the short circuit has been repaired.
Exception xenon lamps: If the short circuit occurred in the circuit of a xenon lamp, the output is permanently switched off after 20 terminal changes.
In this case, the footwell module must be replaced.
Description of dealing with short circuits as of 09/2007:
If a short circuit is detected in a power circuit, this power circuit is switched off after one minute. This power circuit remains switched off until there has been a terminal change (terminal 15 > terminal 30 -> terminal 15).
A renewed attempt to switch on is only made after a terminal change. The control module permanently switches off the corresponding output if a total of 10 terminal changes have taken place while there is a short circuit in a power circuit. After repairing the short circuit, the output is reactivated using a diagnosis command in the test module.
If the short circuit is still present, the output is switched off permanently after another 10 terminal changes.
Exception: xenon lamps: If the short circuit in the circuit of a xenon lamp is still present, the output is switched off again permanently after 4 terminal changes.
An output can be reactivated 5 times by a diagnosis command in the test module. The footwell module permanently switches off the corresponding output if a total of 60 terminal changes have taken place while there is a short circuit in the power circuit.
Exception: xenon lamps: A xenon output can be reactivated 5 times by a diagnosis command in the test module. The footwell module permanently switches off the corresponding output if a total of 24 terminal changes have taken place while there is a short circuit in the power circuit
The output cannot be reactivated even with the diagnosis command and the fault memory entry can no longer be deleted.
In this case, the footwell module must be replaced.